LK Automation Limited LK Automation Limited
Brand: MITSUBISHI
Go Back >> Product Catalogues
RD81MES96 MES interface module
MITSUBISHI RD81MES96 Manual And Instructions
RD81MES96 datasheetPDF datasheet

MITSUBISHI RD81MES96 Product information and technical parameters:
Brand: MITSUBISHI
Name: MES interface module
Model: RD81MES96
"Database sharing.
FA integration solution "e-F@ctory" to achieve development, production, and maintenance of the various stages of the "TCO reduction" as the primary goal,
Effectively utilize advanced technology, optimize the environment of the factory, and explore the future of manufacturing industry.
As the core component of the "e-F@ctory" information sharing products, MES interface through the shared control system and IT system database,
Achieve production efficiency, product quality improvement.
The information collected from the production site is sent directly to the database.
Conditions can monitor the event data in the MES interface side, in the conditions established, send to the database information of work performance data of IT system.
In addition, the MES interface can be used to read data from the database, such as job instructions.
System construction costs reduced by 65%.
Through the use of MES interface, can be directly connected to the programmable controller and database, simplifying the system structure.
In addition, there is no need to use the gateway computer and the program at the time of connection, so compared with the past,
When the system is constructed, the work time and the time limit for a project are reduced. And, by using the high reliability of MES interface,
Can reduce the computer maintenance, maintenance costs. "

Output points: 32 points.
Output form: Transistor (drain type) output.
Rated open and close voltage, current: -.
Rated load voltage: DC12 ~ 24V.
Max load current: 0.2A/ point.
Response time: 1ms.
Common way: 32 point / public end.
Protection function (overload, overheat).
External wiring connection mode: 40 pin connector RD81MES96.
Output module with mechanical relay contact mechanism,
Including the load voltage range of the relay and can be used for the output of the DC12~24V load transistor output type RD81MES96
According to the load voltage, the output points of different, choose the most suitable user needs of the module.
Preventive maintenance based on the life of relay contact.
Relay output module can accumulate the number of ON of each output point RD81MES96.
Through the understanding of the relay contacts of the number of times, according to the relay life of preventive maintenance. Analog input channel number: 16CH.
accuracy
Ambient temperature of 25 plus or minus 5 degrees C: plus or minus 0.1%.
Ambient temperature 0 ~ 55 degrees C:-.
Temperature coefficient: positive and negative 35ppm/.
Common
Conversion speed: 10ms RD81MES96.
Insulation between channels: isolation transformer insulation.
Absolute maximum input: positive and negative 15V, 30mA.
External wiring connection: 40 pin connector two.
Voltage input
The analog input voltage: DC - 10 - 10V.
Digital output value: 32000 ~ 32000.
Current input
Analog input current: DC0 ~ 20mA.
Digital output value: 0 ~ 32000.
Execute event driven program through alarm output
Strengthen the implementation of the interrupt function according to the alarm output flag, easy to carry out preventive maintenance.
The measured value and the change rate of the analog input signal exceed the upper and lower limits of the set,
Regardless of the procedure of the scan time, can be executed interrupt handling, quickly respond to abnormal conditions.
Analog input module for the external analog signal into the interface of the programmable controller.
Can choose the channel between the insulation, voltage input, current input, voltage / current mixed input, thermocouple input, teemperature resistance (RTD) input for a variety of purposes, such as modules RD81MES96.
Filter high frequency interference.
Analog input module has been equipped with a first order lag filter.
The analog input signal with high frequency interferencee component can be obtained by using the first order lag filter RD81MES96.
Parameters can be set through the filter time constant, no program can be easy to use.