MITSUBISHI R60DA4 Product information and technical parameters:
Brand: MITSUBISHI
Name: Analog output module
Model: R60DA4
Analog output channel number: 4CH.
accuracy
Ambient temperature of 25 plus or minus 5 degrees C: plus or minus 0.1%.
Ambient temperature 0 ~ 55 degrees C: plus or minus 0.3%.
Temperature coefficient.
Conversion speed: 80 s/CH.
Channel to channel insulation
Output short circuit protection: have.
External power supply: DC24.
External wiring connection mode: 18 point screw terminal.
Voltage output
Digital input value: 32000 ~ 32000.
Analog output voltage: DC - 10 - 10V.
Current output
Digital input value: 0 ~ 32000.
Analog output current: DC0 ~ 20mA.
The analog output module is the interface of analog signal to the external output through the programmable controller.
Can choose voltage output, current output, voltage / current mixed output type for a variety of purposes of the module.
High speed output flow simulation waveform.
The analog output module has the function of registering arbitrary waveform data to the module, and continuously executing the analog output according to the set conversion cycle.
Execute the analog quantity (torque) control of stamping machine and injection molding machine, can automatically output the control waveform,
Through the process of high speed, smooth control. In addition, only prior to the waveform data are registered in the module,
Can easily control the analog waveform, so the production line control, such as repetitive control,
Without using a special program to create the waveform, can reduce the programming time.

The input and output module installation number: 12.
Can install module: iQ-R MELSEC series module.
DIN guide rail mounting adapter type: R6DIN1.
Size (H) * (32.5mm) * (W) * (D): * 439mm * 101mm.
Substrate module for mounting various modules of iQ-R MELSEC series.
CPU module could not be installed on the extended substrate module R60DA4. "Analog input channel number: 4CH.
Available thermocouple: B, R, S, K, E, J, T, N, U, L, PL II, W5Re/W26Re R60DA4
Available temperature resistance: PT100, JPt100.
Sampling period 4CH: 250ms/500ms.
Control output cycle: 0.5s ~ 100.0s.
Input impedance: 1M.
Input filter (0: input filter OFF): 0 ~ 100s.
Sensor compensation value setting: the full range of the input range of the negative terminal to the full range of the input range R60DA4.
Sensor input when the action: according to the scale of the processing.
Temperature control mode: ON/OFF PID pulse or 2 position control
Heater disconnection detection specification: there.
External wiring connection: 18 point screw terminal two.
Temperature tracking function can be monitored in real time.
Using Works3 GX in the temperature function, can be real-time tracking temperature, in the confirmation of the temperature waveform and parameter adjustment R60DA4.
In addition, the temperature can be saved as a CSV file after the export, the use of a variety of purposes.
Module binding function.
Combined with the use of up to 64 sets of temperature control module for temperature control. Can be combined with the function of the following two points.
Heating function between modules.
Peak current suppression function between modules.
Temperature rising function between modules
By coopperating with the time of arrival of a number of loops, the average temperature is controlled R60DA4.
Can realize the uniform temperature control, avoid partial burning control object,
Part of the phenomenon of thermal expansion. Can be divided intoo 16 groups, with its heating up to the time,
Reduce the overall system in heating up the waste of energy R60DA4. Main base plate, extended substrate mounting.