Capacity: 8MB.Analog input channel number: 8CH.
Cold end compensation accuracy: plus or minus 1.
Available thermocouple: B, R, S, K, E, J, T, N.
Available temperature resistance: -.
Resolution 1:B, R, S, N:0.3
Resolution 2:K, E, J, T:0.1
Conversion speed: 30ms/CH.
Insulation between channels: isolation transformer insulation R120SFCPU.
Disconnection detection: there.
External wiring connection mode: 40 pin connector
R120SFCPU
output
The temperature measurement value (16 bit''signed binary): 2700 ~ 18200.
Zoom value (16 bit with symbol binary).
High speed data sampling is not affected by the scan time.
The analog input module has the function of recording, which can be used to collect the analog quantity input data in the industrial application R120SFCPU.
Can continuously collect data in a set period, each channel can store up to 10000 points of the recorded data.
In addition, the state of the state of any time and data in the program can be changed as a trigger,
To stop collecting data. The analog quantity input data can be stored and maintained before and after the trigger state through the function,
Easy to determine the occurrence of the phenomenon and the collection of test data R120SFCPU. Such as motor testing equipment used in this function.
Control instructions from a programmable controller to a transducer and a power meter transmission test mode,
At the same time, the test data of the test motor is collected at the same time. The input and output module installation number: 12.
Can install module: iQ-R MELSEC series module.
DIN guide rail mounting adapter type: R6DIN1.
Size (H) * (32.5mm) * (W) * (D): * 439mm * 101mm.
Substrate module for mounting various modules of iQ-R MELSEC series.
CPU module could not be installed on the extended substrate module. "Safety grade (SIL): SIL 3 (IEC 61508).
Performance level (PL): e PL (13849-1 EN/ISO).
Operation control mode: stored procedures repeated operation.
Program capacity: 1200K (security program: 40K).
Program memory: 4800K.
Soft element / tag memory: 3370K.
Data memory: 40M.
Unified program development environment.
Whether the general control procedures or safety control procedures, can be integrated into 1 Engineering documents,
Unified management by Works3 GX. The troublesome operation can save more than one project file management.
When you create a security control program, you are also the same as when you create a general control program,
Various features of GXWorks3 can be developed using the support program.
IImprove production efficiency through high responsiveness and rich program capacity R120SFCPU.
Efficient use of high performance iQ-R CC-Link series and IE Field MELSEC networks,
Improve responsiveness and improve production efficiency.
In addition,, the security control program capacity increased to 40K, about 3 times in the past R120SFCPU.
Safe CPU can be used to deal with complex large capacity programs.